Floor insulation requirement as recommended by PART L 2002 of the UK building regulations
| Thickness of floor insulation for solid ground floors to achieve U-value of 0.25 W/m2K. The larger the floor area the less is the insulation thickness. | ||
| Perimeter to Area Ratio P/A | PS Thickness | PU Thickness |
| Up to 0.25 | 50mm | 30 mm |
| From 0.25 to 0.29 | 60mm | 40 mm |
| From 0.29 to 0.345 | 70mm | 45 mm |
| From 0.345 to 0.425 | 80mm | 50 mm |
| From 0.425 to 0.55 | 90mm | 60 mm |
| from 0.55 to 0.73 | 100mm | 65 mm |
For maximum energy saving, we recommend increase in insulation thickness between 20 to 50% when using underfloor heating.
| Thickness of floor iInsulation for suspended beam and block floors to achieve U-value of 0.25 W/m2K. The larger the floor area the less is the insulation thickness. | ||
| Perimeter to Area Ratio P/A | PS Thickness | PU Thickness |
| Up to 0.27 | 50mm | 30 mm |
| From 0.27 to 0.33 | 60mm | 40 mm |
| From 0.33 to 0.44 | 70mm | 45 mm |
| From 0.44 to 0.60 | 80mm | 50 mm |
| From 0.60 to 0.90 | 90mm | 60 mm |
| From 0.90 | 100mm | 65 mm |
The calculations are based on concrete blocks with a lamda
value of 0.18 W/mK